摘要

High-voltage circuit-breakers have to be performed the type tests including short-circuit current making and breaking tests according to the IEC 62271-100(2012) or relevant standards. During the short-circuit tests all kinds of parameters such as currents and voltages (transient and recovery) shall be satisfied in accordance with the relevant standards. There are 5 test duties such as T10, T30, T60, TlOOs and TlOOa for short-circuit current making and breaking tests. Especially, the rising time(t_3) of transient recovery voltage in test duty T10 and T30 is very short and test laboratories in general cannot satisfy this requirement because they have the bigger stray capacitance of transformer than the standards require. Through this paper PT&T would like to study several test circuits and also propose the suitable test circuit that the rising time can be satisfied with the relevant standards.
机译:必须执行高压断路器,包括根据IEC 62271-100(2012)或相关标准的短路电流制作和断裂测试。在短路测试期间,应根据相关标准满足各种参数,如电流和电压(瞬态和恢复)。有5个测试职责,如T10,T30,T60,TLOOS和TLOOA,用于短路电流制作和断裂测试。特别是,测试占空比T10和T30中的瞬态恢复电压的上升时间(T_3)非常短,测试实验室一般不能满足该要求,因为它们具有比标准的变压器的更大杂散电容。通过本文,PT&T希望研究多个测试电路并提出合适的测试电路,即所需的时间可以满足相关标准。

著录项