The NFPA 70E standard — 2012 edition and the CSA Z462-12 standard describe the calculations required to determine the approximated incident energy in a DC arc flash. These calculations assume that the power source for the DC system is linear. This paper describes the calculations required to estimate the incident energy in a DC arc flash for solar farms, where the power source is highly nonlinear. The equations required for the calculation are derived from fundamentals and compared to the equations provided by the above standards. The incident energy levels found in a typical solar farm are presented in an example, where the results obtained by the application of the standards and the proposed method are compared. Recommendations to include in the standards the provisions for the calculation of DC arc flash in solar farms are given in this paper.
机译:NFPA 70E标准 - 2012年版和CSA Z462-12标准描述了确定DC电弧闪光灯中近似的入射能所需的计算。这些计算假设DC系统的电源是线性的。本文介绍了估计DC电弧闪光灯的入射能所需的计算,用于太阳能电池,电源高度非线性。计算所需的方程来自基本原理,并与上述标准提供的等式相比。在一个示例中提出了典型的太阳能电池中发现的事件能量水平,其中通过应用标准和所提出的方法获得的结果。本文给出了在标准中包含在标准中计算太阳能电池中DC电弧闪光的规定。