首页> 外文会议>Conseil International des Grands Reseaux Electriques;International Council on Large Electric Systems;CIGRE session >Bushing Failures with Rapid and Very Rapid Evolution Time Detected by Online Monitoring
【24h】

Bushing Failures with Rapid and Very Rapid Evolution Time Detected by Online Monitoring

机译:通过在线监控检测到具有快速和非常快速的演化时间的套管故障

获取原文

摘要

Because many transformer failures originate at the bushings, and in order to reduce the shutdowns for testing, the offline tests on bushings have been replaced by online monitoring, which has been providing new data on the time of evolution and the way the defects evolve. In general, it was believed that the failures in bushings evolve slowly, in weeks or months. While this is true in many cases, this paper presents the experiences by Brazilian electric power utilities Chesf and Eletrosul, in which online monitoring data indicated defect evolution times of minutes or hours. A new methodology for detection and alarming of rapid evolution defects will be introduced which, when used with the current slow evolution failure detection techniques, will result in an increased reliability of the electric power supply.
机译:由于许多变压器故障是由套管引起的,并且为了减少测试的停机次数,对套管的脱机测试已被在线监控所取代,在线监控已提供了有关演变时间和缺陷演变方式的新数据。通常,人们认为衬套的故障会在几周或几个月内缓慢发展。尽管在许多情况下都是如此,但本文介绍了巴西电力公司Chesf和Eletrosul的经验,其中在线监测数据表明缺陷演变的时间为数分钟或数小时。将介绍一种用于检测和报警快速发展缺陷的新方法,当与当前的缓慢发展故障检测技术一起使用时,它将提高电源的可靠性。