首页> 外文会议>International conference on gas discharges and their applications >IMPACT OF SURFACE CONDITIONS ON CORONA DISCHARGE FOR CHANG-FANG 500KV COMPACT TRANSMISSION LINE WITH A CORONA CAGE
【24h】

IMPACT OF SURFACE CONDITIONS ON CORONA DISCHARGE FOR CHANG-FANG 500KV COMPACT TRANSMISSION LINE WITH A CORONA CAGE

机译:长方500kV紧凑型电晕笼的表面条件对电晕放电的影响

获取原文

摘要

Relatively little investigation has previously been done on the effects of aging on conductor surface conditions, or on the ac corona discharges in the first 500kV compact transmission lines (Changping to Fanshan in Beijing) in China. In the present work these were investigated by means of comparing corona discharge on typical aged conductors with that on new ones. Scanning electron microscopy (SEM) and energydispersive X-ray (EDX) analysis were employed to characterize the surface morphology and composition of the conductors; and a non-contact surface profiler was used to measure the surface roughness of the samples. As a result of corrosion and the adherence of various substances to the conductors, the surface of operated conductor was rougher than the new one. The ac corona discharge characteristics of the conductors were studied in a corona cage using an ultraviolet imaging detector. As a result of the rough surfaces, the corona discharge intensity for the operated conductors was found to be stronger th an that for the new one; and the corona inception voltage for the operated conductor was 8.29% lower than the new one.
机译:以前已经对导体表面条件的老化的影响或在中国的前500kV紧凑型传输线(北京旺山)中的AC电晕放电方面进行了相对较少的调查。在目前的工作中,通过将电晕放电与新的导体进行比较,在新的导体上进行研究。扫描电子显微镜(SEM)和能量消散X射线(EDX)分析用于表征导体的表面形态和组成;并且使用非接触表面分析仪来测量样品的表面粗糙度。由于腐蚀和各种物质对导体的粘附,所操作的导体表面比新的表面更粗糙。使用紫外线成像检测器在电晕笼中研究导体的交流电晕放电特性。由于粗糙表面,发现了操作导体的电晕放电强度更强大的是新的导体;并且操作导体的电晕初始电压比新的4.29%低8.29%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号