Historically, protection voltages utilized in Cathodic Protection ( CP ) programs for gas pipelines have been considered to be DC voltages. However, long pipe runs, especially in proximity to power lines or other protected structures, make the pipes susceptible to undesirable induced voltages. Failure of individual diodes in the CP rectifiers can result in increases in the AC component of the applied voltage. Both of these unplanned electrical environmental circumstances can impact the protection of the pipe, and potentially create unsafe voltages on the pipe structures. This paper provides a basic look at the reality of protection voltages in the field, utilizing current generation wireless remote monitoring processes, showing the potential for remote diagnosis of geographically distributed CP problems.
机译:从历史上看,在气体管道的阴极保护(CP)程序中使用的保护电压一直被认为是直流电压。但是,较长的管道,特别是靠近电源线或其他受保护的结构,使管道容易受到不希望的感应电压的影响。 CP整流器中单个二极管的故障会导致施加电压的AC分量增加。这两种计划外的电气环境都可能影响管道的保护,并有可能在管道结构上产生不安全的电压。本文利用当前的无线远程监控过程,对现场保护电压的实际情况进行了基本的了解,显示了对地理上分布的CP问题进行远程诊断的潜力。