首页> 外文会议>2011 2nd Power Electronics, Drive Systems and Technologies Conference >A comparative study of AC/DC converters used in high current applications
【24h】

A comparative study of AC/DC converters used in high current applications

机译:大电流应用中AC / DC转换器的比较研究

获取原文

摘要

This paper is dedicated to a comparative study between prevailing schematics of rectifiers employed in industry for high current uses. Different configurations are introduced so far but the most common ones are thyristor- controlled rectifiers (ANSI 25–26 and ANSI 45–46). This paper proposes another configuration that is a combination of AC/AC converter, transformer and paralleled diode rectifiers. As an illustration, a comparison is made between the proposed converter and double bridge rectifier (ANSI 45–46) from viewpoint of reactive and harmonic powers and power losses. Current harmonics, harmonic loss factor (FHL), apparent, active, reactive, and distortion powers are extracted for different operating modes of the two converters. It is shown that for the proposed rectifier, RMS value of the current and its harmonics, current THD, and losses including switching, DC and eddy current losses of windings reduce as the firing angle increases. Finally, two descriptive experiments are conducted to verify the theoretical results.
机译:本文致力于对大电流工业使用的整流器原理图之间的比较研究。到目前为止,已经介绍了不同的配置,但最常见的是晶闸管控制的整流器(ANSI 25–26和ANSI 45–46)。本文提出了另一种配置,该配置是AC / AC转换器,变压器和并联二极管整流器的组合。作为说明,从无功功率和谐波功率以及功率损耗的角度对建议的转换器和双桥整流器(ANSI 45-46)进行了比较。针对两个转换器的不同工作模式,提取了电流谐波,谐波损耗因子(F HL ),视在功率,有功功率,无功功率和失真功率。结果表明,对于所提出的整流器,电流的RMS值及其谐波,电流THD以及包括开关的损耗,直流损耗和绕组的涡流损耗都随着触发角的增加而减小。最后,进行了两个描述性实验以验证理论结果。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号