Experimental Study on Energy Efficiency of Heat-source Tower Heat Pump Units in Winter Condition

机译:冬季热源塔式热泵机组能效试验研究

获取原文

摘要

Building energy consumption in China has been increasing rapidly. And a small increase in the operation efficiency of the air-conditioning system can substantially decrease it. In this paper a new type heat pump is developed to improve the performance of conventional air-source heat pumps. The major components of heat-source tower heat pump units are closed-type heat-source tower (cold and heat sources absorption equipment) and heat pump of low temperature heat source. According to the relevant national standards, the thermal parameters were experimentally studied, such as total heating capacity, consumed total power of heating and heating comprehensive performance coefficient, etc. of the heat-source tower heat pump developed for winter condition. Main test results: when air dry bulb temperature is 1°C~5°C, relative humidity is 71%~95%, COP of the chiller can be 2.58-4.34 and SEER of the units can 2.45-3.45 in winter condition. The results indicate that the heat-source tower heat pump units, which is new developed, has very good application prospects in hot summer and cold winter region.
机译:中国的建筑能耗一直在迅速增长。而且,空调系统的运行效率的小幅提高会大大降低空调系统的运行效率。本文开发了一种新型的热泵,以改善常规空气源热泵的性能。热源塔热泵机组的主要部件是封闭式热源塔(冷热源吸收设备)和低温热源热泵。根据相关的国家标准,对冬季开发的热源塔式热泵的总供热能力,供热消耗总功率以及供热综合性能系数等进行了热力参数的实验研究。主要测试结果:风干球温度为1°C〜5°C,相对湿度为71%〜95%时,在冬季,冷水机的COP可以为2.58-4.34,机组的SEER可以为2.45-3.45。结果表明,新开发的热源塔式热泵机组在炎热的夏季和寒冷的冬季地区具有很好的应用前景。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号