This paper deals with a few solutions for reduction of electric and magnetic field emissions caused by the overhead power lines. Calculations carried out for existing high voltage 400 kV overhead lines in Slovenia show that the emissions of electric and magnetic field at the border of overhead line right of way could be too high. For that very reason, the proposed paper, was attempted to minimize the emissions of electric and magnetic fields caused by the overhead line based on rearrangement of its line conductors. The first proposed solution is to change the sequences of conductor placements between both systems of the double-circuit overhead line. The second solution is the usage of higher overhead lines tower, while the third solution is electromagnetic field reduction based on conductor arrangements obtained in an optimization process. In the given case, optimization goal is to find that arrangement of the conductors, where the height of the tower is minimal and while the values of the magnetic and electric fields on the border of the overhead line right of way are under prescribed limits. All calculated results in this work are made for double-circuit overhead power line in the Electric Power Network of Slovenia.
机译:本文讨论了几种减少架空电力线引起的电场和磁场辐射的解决方案。对斯洛文尼亚现有的400 kV高压架空线进行的计算表明,架空线通行权边界处的电场和磁场辐射可能太高。由于这个原因,提出的论文试图基于其导线的重新布置,将架空线引起的电场和磁场的辐射降至最低。提出的第一个解决方案是更改双回架空线的两个系统之间的导体放置顺序。第二种解决方案是使用高架空线路塔,而第三种解决方案是基于在优化过程中获得的导体布置来减少电磁场。在给定的情况下,优化目标是找到导线的布置,其中塔的高度最小,并且架空线边界上的磁场和电场值在规定的范围内。这项工作的所有计算结果都是针对斯洛文尼亚电网中的双回架空电力线得出的。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号