This research aimed at developing a technique for field evaluation of aged 345kV ZnO surge arresters, for identifying suspect equipment with in service failure risk. In this way, material damages, emergency downtime periods and personal hazards could be avoided. After some in service failures in 345kV class ZnO arresters, the analysis of the failed equipment showed burning signs at the ZnO blocks surface inside the failed arrester, probably caused by internal superficial electrical discharge. The surface coating of the ZnO blocks, under high electrical gradient, seemed to have suffered some kind of burning process, in this way creating conductive paths, causing short-circuit and leading to failure. The technique developed in this research was applied successfully in the field, in substation environment, where the identification of surge arresters presenting internal partial discharges activity was possible. All the tests were performed with surge arresters under normal operation with all installation energized.
机译:这项研究旨在开发一种用于对老化的345kV ZnO电涌放电器进行现场评估的技术,以识别具有服务故障风险的可疑设备。这样,可以避免财产损失,紧急停机时间和人身伤害。在345kV级ZnO避雷器发生某些服务故障后,对发生故障的设备进行分析后发现,在发生故障的避雷器内部ZnO块表面有燃烧迹象,这可能是由内部表面放电引起的。 ZnO块的表面涂层在高电梯度下似乎经历了某种燃烧过程,以这种方式形成导电路径,导致短路并导致故障。这项研究中开发的技术已成功应用于变电站环境中,在该环境中,可以识别具有内部局部放电活动的电涌放电器。所有测试均在避雷器在正常运行的情况下进行,所有安装均通电。