The objective of this paper is to investigate how strong the axial magnetic field (AMF) is needed for a 126kV vacuum interrupter at different contact gaps. The AMF was generated by a pair of ⅔ coil AMF contacts. First, the accuracy of the three-dimensional finite element simulation of AMF was validated by an AMF measurement at contact gap 30mm. After that high-current switching experiments with the AMF contacts were carried out at different contact gaps of 20mm and 50mm at 40kA rms. Then the AMF at the contact gaps of 20mm and 50mm was simulated to analyze the interrupting experimental results. The results showed that there was a successful interruption at 40kA with an AMF of 235mT at contact gap 20mm. And current interruption failures occurred with an AMF of 146mT at contact gap 50mm.
机译:本文的目的是研究在不同接触间隙下126kV真空灭弧室需要多强的轴向磁场(AMF)。 AMF是由一对⅔线圈AMF触点产生的。首先,通过在接触间隙30mm处进行AMF测量,验证了AMF三维有限元模拟的准确性。之后,在40kA rms的20mm和50mm的不同接触间隙处进行了AMF触点的大电流开关实验。然后,模拟了接触间隙为20mm和50mm时的AMF,以分析中断的实验结果。结果表明,在接触间隙20mm处,在40kA时成功中断了235mT的AMF。 146mT的AMF在接触间隙50mm处发生了电流中断故障。