Study on the Fluctuations of Cooling Load and Natural Room Temperature of Different Indoor Zones

机译:不同室内区域制冷负荷和自然室温波动的研究

获取原文

摘要

In summer, the cooling load and natural room temperature in large space are usually not uniform. The cooling load and natural room temperature of different indoor zones are investigated by respectively using the improved Radiant Time Series Method (RTS) and the DeST software, which helps with the understanding of the distribution and variations of these parameters. The results indicate that: different indoor zones, though having the same size and internal heat sources, have significantly difference in cooling load and natural room temperature during a calculation day. The reason for that is due to different locations relative to the outdoor environment (sunlight, outdoor sol-air temperature, etc.). The zones adjacent to the envelope always have more cooling load and higher natural room temperature than those of the others. Moreover, this paper has studied some influential parameters such as the area ratio of window to wall, the air change rate and the orientations of the south-facing wall. It can be concluded that: the difference between two zones are more significant with greater area ratio of window to wall, vice versa. Air change rate has great effect on the natural room temperature of the zones; however, it has negligible impact on the room cooling load distribution. The room with less deflection angle has less difference in cooling load and natural room temperature of different zones. Besides, it is found that the two maximum difference appearing in the east-facing rooms is temporally later than that in the west-facing rooms.
机译:在夏季,大空间中的制冷负荷和自然室温通常不均匀。通过使用改进的辐射时间序列方法(RTS)和DeST软件分别研究了不同室内区域的制冷负荷和自然室温,这有助于理解这些参数的分布和变化。结果表明:在计算日内,尽管不同的室内区域具有相同的大小和内部热源,但其制冷负荷和自然室温却存在显着差异。原因是由于相对于室外环境的位置不同(阳光,室外溶胶温度等)。与信封相邻的区域总是比其他区域具有更大的制冷负荷和更高的自然室温。此外,本文还研究了一些影响因素,例如窗与墙的面积比,换气率和朝南墙的朝向。可以得出结论:随着窗墙的面积比增大,两个区域之间的差异更加显着,反之亦然。换气速率对区域的自然室温有很大影响;但是,它对房间制冷负荷分配的影响可忽略不计。偏转角较小的房间在不同区域的冷却负荷和自然室温之间的差异较小。此外,发现在朝东的房间中出现的两个最大差异在时间上比朝西的房间中出现的最大。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号