Very fast transient overvoltage analysis for 400kV GIS

机译:400kV GIS的非常快速的瞬态过电压分析

获取原文

摘要

The very fast transient overvoltage (VFTO) produced during isolator switching operation in EHV GIS substations could impose a potential risk of insulation breakdown in the equipment connected directly to the GIS. A quantitative assessment of the expected VFTO against the VFTO withstand capability of the concerned EHV equipment is necessary for power companies in assessing the risk and formulating appropriate remedial measures to mitigate the risk without unduly limiting the flexibility of switching operations.
机译:在EHV GIS变电站的隔离器切换操作期间产生的非常快速的瞬态过电压(VFTO),可能会对直接连接到GIS的设备造成绝缘击穿的潜在风险。电力公司在评估风险并制定适当的补救措施以减轻风险而又不过度限制开关操作灵活性的情况下,有必要对有关超高压设备的VFTO承受能力进行预期VFTO的定量评估。