Taking the density of lightning strokes and the density of electric poles into account, we calculated outage rates of each equipment of 6.6kV distribution line due to summer(Mar.-Oct.) and winter(Nov.-Feb.) lightning for 6 years in the Chugoku region located in the western part of Japan. The results are summarized as follows. (1)For equipments excluding surge arresters, outage rates due to winter lightning was more than about 10 times as much as that due to summer lightning. (2)Outage rates of surge arresters due to winter lightning was more than about 40 times as much as that due to summer lightning.
机译:考虑到雷击的密度和电极的密度,我们计算了6.6kV配电线路因夏季(3月至10月)和冬季(11月至2月)雷击6年而造成的断电率。位于日本西部的中国地区。结果总结如下。 (1)对于不带电涌放电器的设备,冬季雷电造成的断电率是夏季雷电造成的断电率的约10倍以上。 (2)冬季雷电引起的避雷器断电率是夏季雷电引起的避雷器断电率的40倍以上。