Partial discharge detection using acoustic emission method for a waveguide functional high-voltage cast-resin dry-type transformer

机译:波导功能高电压树脂干式变压器的声发射法局部放电检测

获取原文

摘要

This study adopts the acoustic emission (AE) method to measure partial discharges (PD) in a cast-resin dry-type transformer and proposes a waveguide atop the high-voltage winding of the transformer to improve the propagation of the PD acoustic signals occurring in winding to acoustic emission sensors used. A waveguide is proposed to improve the signalspsila quick attenuation and it also is a safe method for electrical equipments measurement. Finally, a waveguide is practically installed on a cast-resin dry-type transformer; the measurements and the locating of PDspsila AE signals for transformer are carried out. This study demonstrates a feasible new simple, safe and economical solution for diagnosing and locating PDs in the transformer.
机译:这项研究采用声发射(AE)方法来测量铸造树脂干式变压器中的局部放电(PD),并提出了一种在变压器高压绕组上方的波导,以改善在PD变压器中发生的PD声信号的传播。绕线到使用的声发射传感器。提出了一种改善信号快速衰减的波导,它也是电气设备测量的一种安全方法。最后,实际上在铸塑树脂干式变压器上安装了一个波导。进行了变压器PDspsila AE信号的测量和定位。这项研究演示了一种可行的,简单,安全和经济的新解决方案,用于诊断和定位变压器中的局部放电。