Based on the experiment carried out in the lab on several cables in which there are some typical PD models, the relationship between the single acoustic signal generated by the partial discharge and the apparent discharge magnitude in a line frequency cycle are researched. Further more, through the detection system which is combined of the VHF PD detection method and the acoustic emission detection method, the expressions of the relationship between the voltage value, which is gotten directly from the detection system and the apparent discharge magnitude by the curve fitting method. At the same time, the method of locating the defect manually with the acoustic sensor is introduced simply in the paper.
机译:基于实验室对几种典型的局部放电模型的电缆进行的实验,研究了局部放电产生的单声信号与线频率周期中的视在放电量之间的关系。此外,通过将VHF PD检测方法和声发射检测方法相结合的检测系统,可以通过曲线拟合直接从检测系统获得的电压值与视在放电量之间的关系的表达式。方法。同时,本文简单介绍了利用声传感器手动定位缺陷的方法。