Comparison of On-line and Off-line PD Measuring System for Hydro Generator Stator Winding

机译:水轮发电机定子绕组在线和离线局部放电测量系统的比较

获取原文

摘要

Partial discharge (PD) is one of the most promising phenomena to utilize in detecting deterioration of high voltage rotating machine insulation. PD test can be performed either when the machine is not operating (off-line) or during normal machine operation (on-line). Off-line PD test is a well-known method to assess the stator winding insulation and on-line PD test has proven to be a successful technique of monitoring stator insulation condition. This study carried out on-line and the offline PD tests on a hydro-generator using the same PD sensor and measuring instrument and analyzed various PD characteristic parameters. We used the contact-type CC (Ceramic Coupler) sensor for PD tests. To test reliability of this sensor, we analyzed the frequency response characteristic test using S parameter and PD signal characteristic test for the simulated defect winding. Also, we checked the similarity between the test results of diagnostic system (PDMS-HG) was installed on the test hydro generator and of the on-line and off-line PD tests.
机译:局部放电(PD)是用于检测高压旋转电机绝缘劣化的最有希望的现象之一。 PD测试可以在机器不运行(离线)或正常机器运行(在线)时执行。离线PD测试是一种评估定子绕组绝缘的众所周知的方法,在线PD测试已被证明是监测定子绝缘状况的成功技术。这项研究使用相同的PD传感器和测量仪器对水轮发电机进行了在线和离线PD测试,并分析了各种PD特性参数。我们将接触式CC(陶瓷耦合器)传感器用于PD测试。为了测试该传感器的可靠性,我们针对模拟缺陷绕组使用S参数和PD信号特性测试分析了频率响应特性测试。此外,我们检查了在测试水力发电机上安装的诊断系统(PDMS-HG)的测试结果与在线和离线PD测试之间的相似性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号