首页> 外文会议>International conference on properties and applications of dielectric materials >Application of FEM for Understanding the Electric Field Distribution in Copper Sulphide Contaminated Paper-Oil Insulation of Power Transformer
【24h】

Application of FEM for Understanding the Electric Field Distribution in Copper Sulphide Contaminated Paper-Oil Insulation of Power Transformer

机译:有限元的应用,以了解电力变压器硫化铜污染纸 - 纸纸纸 - 纸纸纸 - 储纸 - 储纸 - 蓄水器

获取原文

摘要

Power transformers are failing due to the formation and migration of copper sulphide in to paper insulation. The copper sulphide is formed due to the interaction of sulphur present in the oil with copper conductor. This paper presents FEM simulation of the copper sulphide contaminated model of paper oil insulation and analysis of the consequent field distortions. The results indicate increase in electric stress across paper insulation due to field distortion. An effort is made to validate the experimentally obtained partial discharge inception voltages.
机译:由于硫化铜覆盖纸绝缘材料的形成和迁移,电力变压器失败。由于铜导体中存在的硫的相互作用,硫化铜形成硫化铜。本文介绍了对硫化铜污染模型的FEM模拟纸质污染模型及随后场畸变分析。结果表明由于场失真导致纸质绝缘的电力应力增加。努力验证实验获得的局部放电初始电压。