This work deals with theoretical and experimental investigation concerning the insulation distance reduction of distribution lines, when a stay wire (a steel wire that supports the pole of the distribution network), was heated due to ground fire occurrence. It has been experimentally proven that a ground fire can drastically reduce the mechanical strength of stay wire, up to a point that wire breakage can be caused even from a small ground fire produced by dead wood and small bushes near the wire. Theoretical results lead to the conclusion that the fire causes a permanent expansion on the wire which results in the loosening of the bare conductors.
机译:这项工作涉及关于分配线的绝缘距离减小的理论和实验研究,当支线(支撑分配网络的杆的钢丝)被引起的地面火灾发生时加热。它已经通过实验证明,地火可以大大降低留钢的机械强度,直至电线破损的点,即使是由死木和电线附近的小灌木丛生产的小地火。理论结果导致结论是火导致导线上的永久性膨胀,导致裸导体松动。