Combined Resonance Phenomena due to Earth Wires Grounding and Conductor Sagging Effects in Overhead Transmission Lines

机译:架空输电线路中接地线接地和导体下垂效应引起的组合共振现象

获取原文
获取原文并翻译 | 示例
           

摘要

The periodic discrete bonding of earth wires to ground, on the one hand, and the distributed conductor sagging between towers, on the other, are mechanisms that have been reported before to be individually responsible for abnormal high-frequency responses of overhead power lines. In this paper we consider both effects superposed and then evaluate, as a function of the frequency, the even and odd mode propagation parameters characterizing a given transmission line section. We show that the two interacting mechanisms being combined do not annihilate each other; on the contrary, wave interference effects accumulate giving rise to broadband noticeable resonance phenomena for frequencies such that the line span gets close to one half wavelength, typically in the 400-600 kHz range.
机译:一方面,接地线与地面的周期性离散粘结,另一方面,塔架之间的分布导体下垂,这是以前曾报道过的机制,分别负责架空电力线的异常高频响应。在本文中,我们考虑了这两种效应的叠加,然后根据频率评估表征给定传输线部分的偶数和奇数模式传播参数。我们表明,结合在一起的两个相互作用的机制不会相互消灭;相反,相反,波干扰效应的累积会导致宽带出现明显的频率共振现象,从而使线跨距接近一半的波长,通常在400-600 kHz范围内。

著录项

  • 来源
    《European Transactions on Electrical Power》 |2003年第4期|p.209-217|共9页
  • 作者

    J.A. Brandao Faria;

  • 作者单位

    Centro de Electrotecnia Teorica e Medidas Electricas, Instituto Superior Tecnico, Av. Rovisco Pais, 1049-001 Lisboa/Portugal;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类 发电、发电厂;
  • 关键词

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号