摘要

Using a high-speed frame camera, the behavior of the partial arc on triangular ice samples was studied under AC votlage. The relationship between the radius of partial arc root and the leakage current was determined. Based on the model develoepd in our previous stdies and the resutls obtained in the present work, the model was improved and used to calculated the flashover voltage of ice-covered insulators. This model takes into account the variation of arc root radius with leakage current. It was shown that there was a good concordance between the results calculated from the model and the laboratory results.
机译:使用高速帧相机,研究了在交流电压下三角形冰样品上部分电弧的行为。确定了部分电弧根的半径与漏电流之间的关系。基于先前研究中的develoepd模型和本工作获得的结果,对该模型进行了改进并用于计算覆冰绝缘子的闪络电压。该模型考虑了电弧根半径随泄漏电流的变化。结果表明,从模型计算出的结果与实验室结果之间有很好的一致性。