Development of cooling control technology by just-in-time modeling for power reduction in large-scale data center

机译:大规模数据中心电力降低的立交模型开发冷却控制技术

获取原文

摘要

This study involves the development of a cooling control system utilizing the Just-In-Time (JIT) modeling for the more efficient operation of large-scale data center facilities. In addition, we propose how to control multiple air-conditioning units in order to minimize total power consumption in data center utilizing these predicted data. Data on temperature, humidity and electric power in large-scale data centers were used to generate predicted temperature and humidity for an hour later by JIT modeling. We also estimated the power consumption for air-conditioning units in data center over two months. As a result, it is clear the trend of predicted data is very similar to that of measured one. The accuracy of predicted data utilizing JIT modeling is sufficiently high from the results of calculated correlation coefficient and root mean squared error. The total power consumption for air-conditioning units utilizing proposed control system is found in 6.0% reduction compared with the actually measured data. Since these results were obtained under summer conditions that were the most severe in terms of use of fresh air, further benefits would be expected if a similar study were carried out in other seasons.
机译:该研究涉及利用刚性(JIT)建模的冷却控制系统的开发,以便更有效地进行大规模数据中心设施的操作。此外,我们提出了如何控制多个空调单元,以便利用这些预测数据最小化数据中心的总功耗。大规模数据中心的温度,湿度和电力的数据用于通过JIT建模后一小时产生预测的温度和湿度。我们还估计了两个月数据中心空调单元的功耗。结果,清楚的是预测数据的趋势与测量的数据非常相似。利用JIT建模的预测数据的准确性从计算相关系数和均方根误差的结果充分高。利用所提出的控制系统的空调单元的总功耗被发现与实际测量数据相比,减少了6.0%。由于这些结果是在夏季条件下获得的,因此在使用新鲜空气的使用最严重的情况下,如果在其他季节进行类似的研究,则会预期进一步的益处。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号