首页> 外文会议>Conference on Electrical Insulation and Dielectric Phenomena >A method of deterioration measurement of gap-type arresters for distribution systems
【24h】

A method of deterioration measurement of gap-type arresters for distribution systems

机译:用于分配系统间隙型避雷器的劣化测量方法

获取原文

摘要

ZnO surge arresters with a series gap have been generally applied to 6kV power distribution systems. However, the deterioration diagnostic method of the arresters still has not been sufficiently established in hot-lines. Therefore, we have attempted to establish a method to diagnose the deterioration by measuring the leakage current of arresters. Then, we measured the changes in the respective leakage currents of the arresters and of the series gap with a spacer and the ZnO element of them against the number of operation times when the arresters were operated repeatedly by a large impulse current of 10kA, 4/10 /spl mu/s. In this work, to clarify the cause of the change in the leakage current of the arresters, the inner surface of the spacer is observed by using an X-ray photoelectron spectroscope after the arrester was operated repeatedly by the large current. Then, a method of deterioration measurement of gap-type arresters for distribution systems is proposed.
机译:具有串联差距的ZnO浪涌避雷器通常应用于6kV配电系统。然而,避雷剂的恶化诊断方法仍未充分建立在热线中。因此,我们试图建立一种通过测量避雷器的泄漏电流来诊断劣化的方法。然后,我们测量了阻挡者的各个泄漏电流的变化,以及它们的间隔物和ZnO元素的串联差距,以通过10ka的大冲动电流反复操作时,它们的操作时间倍数是逆时针的次数。 10 / spl mu / s。在这项工作中,为了阐明避雷器的泄漏电流的变化的原因,通过使用大电流重复操作后,通过使用X射线光电子光电子分光镜观察间隔物的内表面。然后,提出了一种用于分配系统的间隙型避雷器的劣化测量方法。