首页> 外文会议>Conference on Electrical Insulation and Dielectric Phenomena >Experimental study on the causes of electrical breakdown of EHV XLPE insulation using 'prebreakdown partial discharge detection method'
【24h】

Experimental study on the causes of electrical breakdown of EHV XLPE insulation using 'prebreakdown partial discharge detection method'

机译:使用“预折杂局部放电检测方法”EHV XLPE绝缘电击的原因实验研究“

获取原文

摘要

The causes of electrical breakdown in EHV XLPE (cross-linked polyethylene) cables were clarified by carrying out the prebreakdown partial discharge (PBPD) detection test under electric stresses from 40 to 70 kV/mm. Ten causes of electrical breakdown were observed in the PBPD test. As expected, it was found that they were associated with very small contaminants and protrusions. The electrical tree inception stress was estimated to be 270 kV/mm on the average. The prebreakdown time was estimated to be on the order of 1 hour under an applied electric field of 5 kV/mm.
机译:通过在40至70kV / mm的电应力下进行预爆地局部放电(PBPD)检测测试,阐明了EHV XLPE(交联聚乙烯)电缆中的电击穿的原因。在PBPD试验中观察到十个电击原因。如预期的那样,发现它们与非常小的污染物和突起有关。电气树初始应力估计平均值为270 kV / mm。预折杂时间估计在5 kV / mm的施加电场下约为1小时。