Integrated nonlinear model of 300 MW power unit for system dynamic performance studies

机译:用于系统动态性能研究的300 MW机组的集成非线性模型

获取原文

摘要

A set of integrated nonlinear dynamic model of 300 MW power unit is set up in MATLAB/SIMULINK with modularization method. The inputs of the model are control signals with 0-1, and the outputs are process variables with engineering unit. To establish the model, the power unit is divided into many parts, the dynamic model of every part is set up and SIMULINK S-functions are designed. According to the characteristics of thermal process, a kind of improved genetic algorithm is introduced to identify the model parameters with operating data of power plant. It is shown by simulation results that the model can reflect the dynamic characteristics factually and can be used to test control system easily.
机译:在MATLAB / SIMULINK中采用模块化方法建立了一套300 MW机组的集成非线性动力学模型。模型的输入是具有0-1的控制信号,输出是具有工程单位的过程变量。为了建立模型,将功率单元分为多个部分,建立每个部分的动态模型,并设计SIMULINK S功能。根据热工过程的特点,引入一种改进的遗传算法,利用电厂的运行数据对模型参数进行辨识。仿真结果表明,该模型能够真实地反映动态特性,可以方便地用于控制系统的测试。