Lightning Performances for AC 500kV Transmission Lines with Quadruple-Circuit on Single Tower

机译:单塔四回路交流500kV输电线路的防雷性能

获取原文

摘要

Lightning stroke fault is one of the most important factors which must be considered when setting transmission lines on high towers. In this paper, some electrical performances for AC 500 kV transmission lines with Quadruple-Circuit on single tower are presented, and lightning performances calculation and analysis are obtained by EMTP (Electromagnetic Transients Program). On the one hand, the impacts of different factors such as impulse ground resistance, etc. on the lightning performances of back flashover are calculated and analyzed in details. Potential waveforms of tower body and cross-arms are presented, as well as voltage waveforms between cross-arms and conductors. On the other hand, lightning performances of shielding failure are studied through changing the mark-height of the tower, shielding angle and other parameters. In the end, measures to improve lightning performance of 500kV AC transmission lines with Quadruple-Circuits are put forward.
机译:雷击故障是在高塔上设置传输线时必须考虑的最重要因素之一。本文介绍了单塔四回路交流500 kV输电线路的一些电气性能,并通过EMTP(电磁暂态程序)获得了雷电性能的计算和分析。一方面,详细计算和分析了脉冲接地电阻等不同因素对后闪击雷电性能的影响。给出了塔架和横臂的电位波形,以及横臂和导体之间的电压波形。另一方面,通过改变铁塔的标志高度,屏蔽角等参数来研究屏蔽失效的雷电性能。最后提出了提高四回路500kV交流输电线路防雷性能的措施。