首页> 外文会议> >Output Voltage Control of A Four-Leg Inverter Based Three-Phase UPS by Means of Stationary Frame Resonant Filter Banks
【24h】

Output Voltage Control of A Four-Leg Inverter Based Three-Phase UPS by Means of Stationary Frame Resonant Filter Banks

机译:基于固定框架谐振滤波器组的基于四腿逆变器的三相UPS的输出电压控制

获取原文

摘要

A method for high performance output voltage control of a four-leg inverter (FLI) based three-phase UPS is proposed. Stationary frame resonant filter bank based output voltage control loop, which is complemented by capacitor current feedback based active damping loop, is employed. Utilizing the zero-state partitioning variable, a generalized form of scalar PWM for the FLI is developed and the minimum loss discontinuous PWM method is derived. The controller and modulator design and implementation details for the FLI-UPS are given. Linear and nonlinear loads for balanced and unbalanced load operating conditions are considered. The scalar control and PWM methods are proven by means of theory, simulations, and experiments.
机译:提出了一种基于四脚逆变器(FLI)的三相UPS的高性能输出电压控制方法。采用基于静态帧谐振滤波器组的输出电压控制环路,并辅之以基于电容器电流反馈的有源阻尼环路。利用零状态分配变量,开发了用于FLI的标量PWM的广义形式,并推导了最小损耗不连续PWM方法。给出了FLI-UPS的控制器和调制器设计以及实现细节。考虑了平衡和不平衡负载运行条件下的线性和非线性负载。标量控制和PWM方法已通过理论,仿真和实验证明。