首页> 外文会议> >Technical and Economical Analysis of Different Measures for Efficient Operation of a Distribution Network in a Mediterranean Island
【24h】

Technical and Economical Analysis of Different Measures for Efficient Operation of a Distribution Network in a Mediterranean Island

机译:地中海岛屿配电网有效运行的不同措施的技术和经济分析

获取原文

摘要

The paper performs a technical and economical comparison of different measures to improve the efficiency of a MV system for power distribution in the Mediterranean island of Lampedusa. The study takes into consideration three possible measures: 1) rated voltage increase from 10 kV to 20 kV; 2) reactive power compensation with fixed capacitor banks; 3) reactive power compensation with switchable capacitor banks. While the study of the first two considered measures is carried out with classical design methods, the optimal reactive design with switchable capacitor banks is carried out by means of a specific software set up at the DIEET and implementing the multiobjective optimization genetic algorithm NSGA-II. The paper reports the results of the study, giving particular importance to the formulation of the optimization problem through the NSGA-II algorithm, that, also in this case, proves to be a powerful investigation tool.
机译:本文对不同措施的技术和经济性进行了比较,以提高地中海中的兰佩杜萨岛的中压配电系统的效率。该研究考虑了三种可能的措施:1)额定电压从10 kV增加到20 kV; 2)使用固定电容器组的无功功率补偿; 3)使用可切换电容器组的无功功率补偿。用经典的设计方法对前两种考虑的措施进行研究,同时通过在DIEET上安装的特定软件并实现多目标优化遗传算法NSGA-II来进行具有可切换电容器组的最优无功设计。该论文报告了研究结果,特别重视通过NSGA-II算法提出优化问题的方法,在这种情况下,NSGA-II算法也被证明是一种强大的研究工具。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有