Preventive and corrective operation of FACTS devices to cope with a single line-faulted contingency

机译:FACTS设备的预防性和纠正性操作,以应对单个线路故障的意外情况

获取原文

摘要

This paper presents how to find proper operating points of FACTS devices to enhance the steady-state security level considering line contingency analysis. Three generic types of FACTS devices such as series controllers shunt controllers, and series-shunt controllers are introduced and applied to enhance a security margin and to minimize security indices. Quantities (MW) of security margin are depicted in a PV curve and security indices related to line flows and bus voltages are utilized and minimized iteratively in this paper. Contingency analysis is performed to detect the severest line fault in a power system. In this system condition, FACTS devices are tested to establish appropriately preventive or corrective action without generation re-dispatching or load shedding. The FACTS operation scheme is verified on the 9-bus system and the IEEE 57-bus system in a line-faulted contingency.
机译:本文介绍了如何通过线路偶然性分析找到合适的FACTS设备工作点,以提高稳态安全级别。引入并应用了三种通用类型的FACTS设备,例如串联控制器,并联控制器和串联并联控制器,以增强安全裕度并使安全指标最小化。在PV曲线中描绘了安全裕度的数量(MW),并且迭代地利用和最小化了与线路流量和母线电压相关的安全性指标。进行应变分析以检测电力系统中最严重的线路故障。在这种系统条件下,对FACTS设备进行了测试,以建立适当的预防或纠正措施,而无需重新发电或降低负荷。 FACTS操作方案已在发生线路故障的9总线系统和IEEE 57总线系统上得到验证。