首页> 外文会议> >Robust temperature control of MSF desalination plants with coefficient diagram method
【24h】

Robust temperature control of MSF desalination plants with coefficient diagram method

机译:用系数图法对MSF海水淡化厂进行稳健的温度控制

获取原文

摘要

Design of a controller sufficiently robust to the parametric uncertainties for the plant parameters is an important problem. Coefficient diagram method (CDM) is shown to be an efficient control technique to solve this problem. The controller design by CDM is based on the choice of the coefficients of the characteristic polynomial of the closed loop system according to the convenient performance criteria such as equivalent time constant, and stability indices. In this study, the controllers are designed for three temperature loops of large multi-stage flash (MSF) desalination system by using CDM; then, obtained time domain characteristics are compared with the results of some other methods, It is shown that CDM design is more stable and robust whilst giving the desired time domain system performance.
机译:一个对工厂参数的参数不确定性足够鲁棒的控制器的设计是一个重要的问题。系数图方法(CDM)被证明是解决此问题的有效控制技术。 CDM的控制器设计基于闭环系统特征多项式的系数的选择,该系数是根据方便的性能标准(例如等效时间常数和稳定性指标)进行选择的。在这项研究中,控制器是通过CDM设计用于大型多级闪蒸(MSF)海水淡化系统的三个温度回路的。然后,将获得的时域特性与其他方法的结果进行比较。结果表明,CDM设计更稳定,更健壮,同时提供了所需的时域系统性能。