首页> 外文会议> >Cable impedance calculations with parallel circuits and multi-neutral returns in distribution networks
【24h】

Cable impedance calculations with parallel circuits and multi-neutral returns in distribution networks

机译:配电网中并联电路和多中性回路的电缆阻抗计算

获取原文

摘要

This paper addresses impedance calculations in distribution networks. Two sets of paralleled, three-phase conductors with concentric neutrals and also a separate neutral are considered. An approximate method to calculate the impedance for this configuration is to calculate the impedance for one three-phase set of conductors, and then to divide this result by two. This paper compares this common practice with a more exact calculation that considers the mutual coupling between two sets of three-phase conductors. Errors in the current practice are shown to be significant. Comparisons are made for both phase and sequence impedances. Also, a common configuration of parallel conductors of different types is studied. It is shown that the approximate method may have up to 30% errors in the positive sequence impedance and power flows.
机译:本文介绍了配电网中的阻抗计算。考虑了两组具有同心中性点的平行三相导体,以及一个单独的中性点。计算此配置阻抗的一种近似方法是计算一组三相导体的阻抗,然后将该结果除以二。本文将这种常规做法与更精确的计算进行了比较,该计算考虑了两组三相导体之间的相互耦合。当前实践中的错误被证明是重大的。比较相位阻抗和顺序阻抗。而且,研究了不同类型的并联导体的通用构造。结果表明,近似方法在正序阻抗和功率流中可能有高达30%的误差。