Nuclear Power Generating Stations utilize cable trays to route cables that are part of safety related systems. While these trays are predominantly ladder type (ventilated), there are several instances where solid bottom trays, with or without covers, are also applied. The guidance, to determine the ampacity of cables installed in ventilated or solid bottom trays without covers is given in Section 318-11 of the National Electric Code. Guidance to determine the ampacity of cables installed in ventilated or solid bottom trays with covers is also given under "Provision 2" of this same article which states, "a derating of not over 95% of the allowable ampacities for uncovered trays recommended". However, adequate justification to this derating factor is not presented. Due to lack of any industry guidance to determine ampacity of cables in solid bottom trays (with or without covers) the authors performed the required analyses. A summary of the analytical techniques used and the derating factors applicable to the solid bottom trays are presented.
机译:核电站利用电缆桥架布线电缆,这些电缆是安全相关系统的一部分。虽然这些托盘主要是梯形(通风),但在某些情况下,也可以使用带盖或不带盖的实心底部托盘。 《确定国家电气规范》第318-11节中提供的指南,用于确定安装在通风或坚固的无底盖底盘中的电缆的载流量。同一条款的“规定2”中还提供了确定安装在通风或实心底盖带盖托盘中的电缆载流量的指南,该条规定:“建议对不裸露的托盘降额不超过额定载流量的95%”。但是,没有提供有关此降额因数的充分理由。由于缺乏确定硬质底部托盘(带盖或不带盖)中电缆载流量的任何行业指南,因此作者进行了所需的分析。总结了所使用的分析技术和适用于实心底部塔板的降额因素。