首页> 外文会议> >Sensitivity improvement of the digital differential relay for internal ground fault protection in the power transformer with tap changer
【24h】

Sensitivity improvement of the digital differential relay for internal ground fault protection in the power transformer with tap changer

机译:带分接开关的电力变压器中用于内部接地故障保护的数字差分继电器的灵敏度提高

获取原文

摘要

A new method for improving the sensitivity of the digital differential relays that used to detect the internal ground fault in the (/spl Delta/-Y) power transformer with on-load tap changer is presented in this paper. The suggested method can be applied to the digital relays and/or may be applied to the conventional differential relays. Digital differential relay is sensitive to internal faults, except the ground fault, due to the high current ratio required for transformer with tap changer. This is true especially for percentage differential relay. The adopted method deals with this case to increase the number of protected winding against ground faults from 35% to about 100%.
机译:提出了一种提高数字差分继电器灵敏度的新方法,该方法用于检测有载分接开关在(/ spl Delta / -Y)电力变压器中的内部接地故障。所建议的方法可以应用于数字继电器和/或可以应用于常规的差动继电器。由于带分接开关的变压器需要高电流比,因此数字差分继电器对内部故障(接地故障除外)均敏感。对于百分比差动继电器尤其如此。在这种情况下,采用的方法可以将针对接地故障的保护绕组的数量从35%增加到大约100%。