Underground mining is characterized by space constraints forcing the use of long cables to feed large machines, where the application of variable speed drives can generate overvoltages at the machine terminals. This paper presents the analysis and mitigation of harmful overvoltages detected in inverter-fed 1400 HP 13.8 KV motors used for air ventilation in an underground mine. The possible causes of the overvoltages, namely wave reflection and resonance are described theoretically and simulated. On-site direct voltage measurements at the 13.8 kV motor terminals confirmed that resonance was the dominant phenomenon. Based on this study a suitable low-pass filter was designed, constructed and installed. Finally, the adequate operation of such filter is demonstrated by further on-site measurements.
机译:地下采矿的特点是空间有限,迫使使用长电缆给大型机器供电,而变速驱动器的应用会在机器终端产生过电压。本文介绍了分析和缓解在地下矿井中用于通风的逆变器供电的1400 HP 13.8 KV电动机中检测到的有害过电压。理论上描述并模拟了过电压的可能原因,即波反射和共振。在13.8 kV电机端子上的现场直流电压测量结果证实了共振是主要现象。基于这项研究,设计,构建和安装了合适的低通滤波器。最后,进一步的现场测量证明了这种过滤器的正常运行。