首页> 外文会议> >Causes and effects of unbalanced voltages serving an induction motor
【24h】

Causes and effects of unbalanced voltages serving an induction motor

机译:为感应电动机提供不平衡电压的原因和影响

获取原文

摘要

A common requirement of a distribution system is to serve a combination of single-phase lighting loads and three-phase induction motors. Two transformer connections for providing this combination service are the ungrounded wye-delta and the open wye-open delta. Each connection has its good points and bad points. Of concern are the three-phase voltages provided the induction motor. If the voltages are unbalanced, depending upon the degree of unbalance, the induction motor is subject to overheating. Sources of the voltage unbalance can be the unequal spacing between conductors of the primary and secondary lines, the transformer ratings and connection and the amount of single-phase load relative to the three-phase load. This paper utilizes previously published models of the primary and secondary lines, transformer connections and induction motors. A simple system is developed to demonstrate the voltage unbalance created by these components under normal and abnormal conditions and the effect of the resulting unbalances on the induction motor. The system model also provides an insight into the voltages that can appear across the transformer terminals during abnormal operating conditions.
机译:配电系统的普遍要求是为单相照明负载和三相感应电动机提供服务。提供此组合服务的两个变压器连接是不接地的星形-三角形和星形-三角形。每个连接都有其优点和缺点。关注的是感应电动机提供的三相电压。如果电压不平衡,则取决于不平衡的程度,感应电动机会过热。电压不平衡的根源可能是初级和次级线路的导体之间的间距不相等,变压器的额定值和连接以及相对于三相负载的单相负载量。本文利用先前发布的初级和次级线路,变压器连接和感应电动机的模型。开发了一个简单的系统来演示这些组件在正常和异常条件下产生的电压不平衡,以及由此产生的不平衡对感应电动机的影响。该系统模型还提供了在异常运行条件下跨变压器端子出现的电压的见解。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号