首页> 外文会议> >Design study of cooling water system for a large scale linear collider
【24h】

Design study of cooling water system for a large scale linear collider

机译:大型直线对撞机冷却水系统设计研究

获取原文

摘要

A distributed cooling water system was designed for a large scale linear collider. It consists of a large number of small cooling water units and several main cooling systems. One small unit is installed for each RF unit of the main linac. The heat removed from the accelerator is transferred from the small unit to the main cooling system through a heat exchanger and moved to a cooling tower outside the accelerator tunnel. The fine temperature control is carried out in each small unit by utilizing waste heat from klystrons and a small electric heater. A prototype unit was made and has shown that the temperature of cooling water can be controlled within /spl plusmn/0.03/spl deg/C.
机译:分布式冷却水系统设计用于大型线性撞机。它包括大量小型冷却水单元和几个主冷却系统。为主LINAC的每个RF单元安装了一个小单位。从加速器移除的热量通过热交换器从小单元转移到主冷却系统,并移动到加速器隧道外部的冷却塔。通过利用来自克利克朗的废热和小型电加热器,在每个小型单元中进行细温控制。制作了原型单元,并表明冷却水的温度可以控制在/ SPL PLUSMN / 0.03 / SPL DEG / C内。