首页> 外文会议> >Assessment of lead-acid battery state of charge by monitoring float charging current
【24h】

Assessment of lead-acid battery state of charge by monitoring float charging current

机译:通过监控浮动充电电流评估铅酸电池的充电状态

获取原文

摘要

In 1988, one user of flooded Pb-acid secondary batteries in a nuclear power plant began to measure float current in addition to specific gravity readings. A total of 780 cells were monitored. The results of this experience are summarized in this paper. A review of some of the electrochemistry involved is also presented. The analysis of the collected data has led to the conclusion that float current monitoring is preferred over specific gravity readings for assessing the state of charge of a Pb-acid battery. Now the problem turns to the availability of cost-effective, accurate provisions for measuring float current. The last part of this paper presents a test instrument design specifically for taking float current readings.
机译:1988年,一个核电厂中一个充满铅酸二次电池的用户开始测量浮力电流以及比重读数。总共监测了780个细胞。本文总结了这种经验的结果。还介绍了所涉及的一些电化学。对收集到的数据进行分析得出的结论是,在评估铅酸蓄电池的充电状态时,浮力电流监测优于比重读数。现在,问题转向了用于测量浮置电流的具有成本效益的准确配置。本文的最后一部分介绍了一种专门用于获取浮点电流读数的测试仪器设计。