首页> 外文会议> >Calculation of transient parameters and overvoltages in cable/GIS power systems
【24h】

Calculation of transient parameters and overvoltages in cable/GIS power systems

机译:计算电缆/ GIS电力系统中的暂态参数和过电压

获取原文

摘要

In this paper, the present different calculation methods of cable/GIS parameters, including analytical methods, the finite element method, and the subdivision method, are analyzed and compared. With example calculations, suitable methods are recommended. The surface subdivision method is presented for the first time to calculate parameters at high frequencies and is shown to be both simple and convenient. This paper presents the pathological problem that exists at high frequency in the modal transformation of cable/GIS systems. This pathological problem is solved in this paper by removing the pathological elements in modal transformation. With the transient parameters calculated, the influence of the earth on the surge propagation along the cable is also analyzed. The cable sheath is considered as one conductor to reflect the strong effect of the earth. The results of calculations for lightning surge overvoltages in urban cable/GIS systems show that three-phase models should be used instead of one-phase.
机译:本文分析和比较了目前不同的电缆/ GIS参数计算方法,包括分析方法,有限元方法和细分方法。通过示例计算,推荐合适的方法。首次提出了表面细分方法来计算高频参数,并且显示出既简单又方便。本文提出了电缆/ GIS系统模态转换中高频存在的病理问题。本文通过消除模态转换中的病理因素解决了这一病理问题。通过计算瞬态参数,还分析了地球对电涌沿电缆传播的影响。电缆护套被认为是反映大地影响的一种导体。城市电缆/ GIS系统中雷电浪涌过电压的计算结果表明,应使用三相模型而不是一相模型。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有