首页> 外文会议> >A partial discharge monitor for the measurement of partial discharges in a high voltage plant by the transient earth voltage technique
【24h】

A partial discharge monitor for the measurement of partial discharges in a high voltage plant by the transient earth voltage technique

机译:局部放电监测仪,用于通过瞬时接地电压技术测量高压设备中的局部放电

获取原文

摘要

Several proprietary discharge detectors are available that are suitable for measuring the magnitudes of the partial discharges in plants such as high voltage metalclad switchgear. Their main disadvantages are the high capital cost of the test equipment and the complexity of the testing procedure. When performing such tests, the plant must be switched out, connections must be made to the high voltage conductors of the plant under test and high voltages applied from a test set. A 'sanction for test' is therefore required. This overhead may be acceptable when testing primary or grid substations. However, for discharge measurements to be widely applicable it is essential that the tests can be made with the plant live and under load. The Transient Earth Voltage or TEV measurement technique has been developed to fulfil this requirement.
机译:有几种专有的放电检测器适用于测量工厂中局部放电的大小,例如高压金属包覆的开关设备。它们的主要缺点是测试设备的高投资成本和测试过程的复杂性。执行此类测试时,必须将设备关闭,必须将设备连接到被测设备的高压导体,并从测试设备施加高压。因此需要“测试制裁”。测试主变电站或电网变电站时,此开销可能是可以接受的。但是,要使排放量测量能够广泛应用,必须在设备带电和带负载的情况下进行测试。已经开发出瞬态接地电压或TEV测量技术来满足这一要求。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号