Inappropriate setting of the degraded voltage relays at commercial nuclear power plants has subjected the class 1E loads to voltages below their operating range and caused spurious actuation of the undervoltage protection scheme as indicated in the referenced information notices. The authors present a methodology that can be successfully used to eliminate such concerns. A similar method has been used at Nine Mile Point Unit 2 (NMP2). This methodology is generic and can be effectively used in other nuclear power plants. Historically, electrical protection schemes do not use tolerances in accordance with the guidelines provided in Regulatory Guide 1.105. It is noted that application of these guidelines for selection of the degraded voltage relay setpoint and reset value will ensure adequate voltages for all class 1E loads and eliminate nuisance tripping.
机译:在商用核电站中,降压继电器的设置不当已使1E级负载承受的电压低于其工作范围,并且导致了欠压保护方案的虚假启动,如参考信息声明中所示。作者提出了一种可以成功用于消除此类担忧的方法。九英里积分单元2(NMP2)使用了类似的方法。这种方法是通用的,可以有效地用于其他核电厂。从历史上看,电气保护方案不使用根据法规指南1.105中提供的准则的公差。请注意,应用这些准则选择降级的电压继电器设定点和复位值将确保为所有1E类负载提供足够的电压,并消除了讨厌的跳闸。