首页> 外文会议> >Instantaneous feedback in voltage source inverters: a comparative study between nonlinear and linear approach
【24h】

Instantaneous feedback in voltage source inverters: a comparative study between nonlinear and linear approach

机译:电压源逆变器中的瞬时反馈:非线性与线性方法的比较研究

获取原文

摘要

Voltage source inverters used in UPS systems feeding nonlinear loads must be capable of providing an output voltage waveform of quality in spite of all line and load disturbances. Switching algorithms applying output filter state feedback in order to control the instantaneous output voltage are discussed and two approaches are compared. In the case of the nonlinear controller, the driving force is switched at maximum amplitude into the output filter, while the linear discrete-time controller encompasses a synchronous pulse-width modulator placed in the feedback loop. The former gives a higher tolerance level to load disturbances, but encourages randomness in commutations. Simulations and experiments performed show that the latter combines both excellent dynamic performance and synchronous switching. Theoretical background and design considerations are included for both solutions.
机译:尽管受到所有线路和负载干扰,但用于UPS系统中的,为非线性负载供电的电压源逆变器必须能够提供高质量的输出电压波形。讨论了应用输出滤波器状态反馈来控制瞬时输出电压的开关算法,并比较了两种方法。对于非线性控制器,驱动力以最大幅度切换到输出滤波器中,而线性离散时间控制器则包含一个放置在反馈回路中的同步脉宽调制器。前者对负载干扰具有较高的容忍度,但会促进换向中的随机性。进行的仿真和实验表明,后者结合了出色的动态性能和同步开关。两种解决方案均包括理论背景和设计注意事项。