This paper describes a new economical sag/swell voltage generator suitable to the evaluations of high power custom power devices such as DVR (Dynamic Voltage Restorer) and DSTATCOM (Distribution Static Compensator). Proposed system was designed to generate the several power quality disturbances in MVA power ratings - sag, swell, under voltage, over voltage and harmonic distortions. The sag and the under voltage can be generated by voltage drop across a reactor, while its magnitude and durations can be controlled by the firing angle of TCR (Thyristor Controlled Reactor). In the case of the swell and the over voltage, we need a step-up transformer. Output of the step-up transformer is regulated by TCR to obtain nominal voltage level. At any given instant, if the firing angle of TCR is retarded or stopped, then we can obtain the swell voltage or the over voltage disturbance. Also we can generate harmonic current by controlling firing angles of TCR, while keeping the system voltage level within the specified limits. In this paper, two identical three-phase wye-connected TCRs are connected to the secondary windings of two step-down transformers, one operated from wye-wye transformer, the other from delta-wye transformer. Harmonic filters (11th and 13th) are added to reduce the voltage distortion when TCRs are operated. Simulation results are given for several cases of voltage sag and swell generations. Design guidelines are given for the TCR. Finally, conclusions are given.
机译:本文介绍了一种新型的经济型突降/骤升电压发生器,适用于评估DVR(动态电压恢复器)和DSTATCOM(配电静态补偿器)等大功率定制功率设备。拟议的系统旨在产生MVA额定功率中的几种电能质量扰动-骤降,骤升,欠压,过压和谐波失真。骤降和欠电压可以通过电抗器两端的压降产生,而其大小和持续时间可以通过TCR(晶闸管控制电抗器)的触发角来控制。在出现浪涌和过压的情况下,我们需要一个升压变压器。 TCR调节升压变压器的输出以获得标称电压电平。在任何给定的时刻,如果TCR的触发角被延迟或停止,那么我们就可以得到膨胀电压或过电压干扰。同样,我们可以通过控制TCR的触发角度来产生谐波电流,同时将系统电压保持在规定的限值之内。在本文中,将两个相同的三相星形连接的TCR连接到两个降压变压器的次级绕组上,一个由星形-星形变压器工作,另一个由三角形-星形变压器工作。添加了谐波滤波器(第11 和第13 th )以减少TCR运行时的电压失真。给出了几种电压骤降和突增情况的仿真结果。给出了TCR的设计指南。最后给出结论。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号