摘要

This paper presents a root cause analysis of a ground differential (restricted earth fault) protection misoperation including detailed description of the protection scheme, CT characteristics, and computer simulations performed to determine causes and solutions. High power laboratory tests were conducted to verify the simulation results in actual conditions and to compare effectiveness of the restricted earth fault protection design and operation using an overcurrent relay and a multifunction relay.
机译:本文介绍了接地差动(接地故障)保护误操作的根本原因分析,包括保护方案的详细说明,CT特性以及为确定原因和解决方案而执行的计算机模拟。进行了大功率实验室测试,以验证实际条件下的仿真结果,并比较使用过电流继电器和多功能继电器的受限接地故障保护设计和操作的有效性。