Analysis of restricted earth fault relay application within a shunt capacitor bank design impacting on protection stability

机译:分流电容器组设计中受限接地故障继电器应用分析对保护稳定性的影响

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

This research is aimed at analyzing the performance of the restricted earth fault relay used on a 400kV capacitor bank scheme used on the Eskom Transmission network. After the commissioning of two Capacitor Banks using the above mentioned scheme design the plant was energized. As a result of the energization the Shunt Capacitor Bank (SCB) then experienced spurious trips. The cause of the trips was found to be the operation of the restricted earth fault relay. In this research project, restricted earth fault protection on SCBs in the Eskom Transmission environment will be the area of interest. The proposed research will analyze the current SCB protection scheme in service specifically looking at the restricted earth fault circuit design and relay performance. An equivalent model of the SCB from primary plant perspective based on theory will be derived. Recording and analyzing of Comtrade transient waveforms respectively, when the bank is nergized, will be done in order to provide a reference base to work from. Manual alculations of various parameters from the derived model including transient inrush currents and fault currents will be performed to access applicable scheme parameters. Further calculations will include the voltage setting for the restricted earth fault relay. As a result of the analysis a recommendation will be made on a viable solution or a revised design will be put forward, based on the results, to improve the scheme’s performance. The protection scheme is used on the two 400kV 100MVAR capacitor banks 11 and 12 at Hydra Substation.
机译:本研究旨在分析在Eskom传输网络上使用的400kV电容器组方案上使用的受限接地故障继电器的性能。在使用上述方案设计调试了两个电容器组之后,给工厂通电。通电的结果是,并联电容器组(SCB)经历了误跳闸。发现跳闸的原因是受限制的接地故障继电器的操作。在此研究项目中,Eskom传输环境中的SCB的受限接地故障保护将是关注的领域。拟议的研究将着眼于受限的接地故障电路设计和继电器性能,分析当前使用中的SCB保护方案。将从理论出发,从初级工厂的角度推导SCB的等效模型。当库被加电时,将分别记录和分析Comtrade瞬态波形,以便为工作提供参考依据。将手动执行衍生模型中各种参数的计算,包括瞬态浪涌电流和故障电流,以访问适用的方案参数。进一步的计算将包括限制接地故障继电器的电压设置。分析的结果将针对可行的解决方案提出建议,或根据结果提出修订的设计,以提高方案的性能。该保护方案用于Hydra变电站的两个400kV 100MVAR电容器组11和12。

著录项

  • 作者

    Minkley Warick;

  • 作者单位
  • 年度 2013
  • 总页数
  • 原文格式 PDF
  • 正文语种 English
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号