首页> 外文会议>International Symposium on Heat Transfer Enhancement and Energy Conservation(ISHTEEC) vol.1; 20040112-15; Guangzhou(CN) >THEORETICAL ANALYSIS OF INDIRECT EVAPORATIVE COOLER WITH SEPARATE TYPE HEAT PIPE APPLIED ON VENTILATION
【24h】

THEORETICAL ANALYSIS OF INDIRECT EVAPORATIVE COOLER WITH SEPARATE TYPE HEAT PIPE APPLIED ON VENTILATION

机译:通风用独立式热管间接蒸发冷却器的理论分析

获取原文
获取原文并翻译 | 示例

摘要

A mathematical model has been developed and solved on heat recovery in ventilation coupled with indirect evaporation cooling (IEC). The performance of the system is simulated with and without evaporative cooling. The effects of several parameters such as the inlet temperature and the relative humidity of the secondary air stream are investigated. It is shown that a higher inlet temperature of the primary air stream, a lower inlet temperature of the secondary air stream and a lower inlet relative humidity of the secondary air stream lead to a higher effectiveness of the indirect evaporative air cooler. The investigation reveals that the precooling of the air is enhanced with evaporative cooling and results in lower cooling operation and initial equipment costs and a saving in peak demand charges.
机译:已经建立了数学模型,并求解了通风与间接蒸发冷却(IEC)相结合的热量回收问题。在有和没有蒸发冷却的情况下,都对系统的性能进行了仿真。研究了诸如进气温度和二次空气相对湿度等几个参数的影响。示出的是,一次空气流的较高入口温度,二次空气流的较低入口温度和二次空气流的较低入口相对湿度导致间接蒸发式空气冷却器的更高效率。调查显示,蒸发冷却增强了空气的预冷,从而降低了冷却操作和初始设备成本,并节省了高峰需求费用。