Synchronous sampling data is considered as a basic condition for correct operation of all kinds of differential protections in a substation. It is necessary to test it in the substation commissioning procedure. This paper first addresses the root causes of synchronization problems and the necessity of onsite synchronization test for line differential protections and all distributed sampling differential protections in a smart substation. Then a method based on precise time-setting is proposed to test sampling synchronization of differential protections, which can solve difficulties of on-site synchronization test of distributed electrical data. Specific implementations are given and the causes of error are also analyzed in this paper. In a real 500kV smart substation project, error of data synchronization is controlled under 1.5 ° by testing line differential protections and the whole sampling circuit based on the method, which entirely meets the performance requirements of differential protections.
机译:同步采样数据被视为变电站中各种差动保护正确运行的基本条件。有必要在变电站调试过程中对其进行测试。本文首先讨论了同步问题的根本原因,以及在智能变电站中对线路差动保护和所有分布式采样差动保护进行现场同步测试的必要性。提出了一种基于精确时间设定的差动保护采样同步测试方法,解决了分布式电气数据现场同步测试的难题。给出了具体的实现方法,并分析了错误原因。在一个实际的500kV智能变电站项目中,通过测试线路差动保护和基于该方法的整个采样电路,将数据同步误差控制在1.5°以内,完全满足差动保护的性能要求。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号