The study and modelling of chlorine decay in distribution systems has been the subject of intense research in the last decade. This paper reports on a series of experiments carried out on a lifescale test rig in order to quantify any possible effect of hydraulic transients on residual chlorine concentrations in drinking water, comparatively to the decay in steady-state flow conditions. The results relate to two types of tests: steady-state tests were run in order to investigate the decay of residual chlorine during steady-state flow, for varying values of the Reynolds number; transient tests comprised an initial steady-state period, followed by successive transient events and a new steady-state period. The transient events were induced by rapid valve closing manoeuvres. The series of results obtained provide evidence towards the existence of a slowing down effect of hydraulic transients on chlorine decay rates, for the conditions represented by the experiment.
机译:在过去的十年中,配电系统中氯衰减的研究和建模一直是研究的主题。这篇论文报道了一系列在生命规模试验台上进行的实验,目的是量化水力瞬变对饮用水中残余氯浓度(相对于稳态流量条件下的衰减)的任何可能影响。结果涉及两种类型的测试:为了研究雷诺数的变化值,进行稳态测试以研究稳态流动过程中残余氯的衰减。瞬态测试包括一个初始稳态周期,然后是连续的瞬态事件和一个新的稳态周期。瞬时事件是由快速的阀门关闭动作引起的。在实验所代表的条件下,获得的一系列结果提供了证据,表明存在水力瞬变对氯衰减速率的减慢效应。