首页> 外文会议>IEEE PES General Meeting, Conference & Exposition >Study on a Mal-opertaion case of differential protection due to the interaction between magnetizing inrush and sympathetic inrush
【24h】

Study on a Mal-opertaion case of differential protection due to the interaction between magnetizing inrush and sympathetic inrush

机译:励磁涌流与交感涌流相互作用引起的差动保护误动案例研究

获取原文

摘要

Sympathetic inrush is one of the most important topics for relay protection, which has adverse effects on transformer protection. This paper takes a local mal-operation case as an example to analyze the principle of the interaction between magnetizing inrush (M.I) and sympathetic inrush (S.I) and discusses the decay characteristic of magnetizing inrush in high impedance transformer. By means of introducing a new concept of acting factor to describe the decay velocity of magnetizing inrush in a quantitative way, it is found that sympathetic inrush can affect magnetizing inrush decay rate significantly even when the sympathetic inrush is small. The interaction between magnetizing inrush (M.I) and sympathetic inrush (S.I) is the main reason for the mal-operation. In the end, countermeasures are put forward to avoid the mal-operation and a large number of MATLAB simulations prove the countermeasures to be reasonable.
机译:同情浪涌是继电保护的最重要主题之一,对变压器保护有不利影响。本文以一个局部故障案例为例,分析了励磁涌流(M.I)与交感涌流(S.I)之间相互作用的原理,并讨论了高阻抗变压器励磁涌流的衰减特性。通过引入一种新的作用因子概念来定量描述磁化涌流的衰减速度,发现即使在较小的情况下,同感涌流也会显着影响磁化涌流的衰减率。励磁涌流(M.I)和交感涌流(S.I)之间的相互作用是发生故障的主要原因。最后提出了避免误操作的对策,大量的MATLAB仿真证明了该对策是合理的。