首页> 外文会议>IEEE Manchester PowerTech >Stochastic assessment of voltage unbalance due to single-phase-connected solar power
【24h】

Stochastic assessment of voltage unbalance due to single-phase-connected solar power

机译:太阳能单相连接引起的电压不平衡的随机评估

获取原文

摘要

A stochastic method is presented in this paper to estimate the future voltage unbalance in a low-voltage distribution network with high-penetration of single-phase photovoltaic inverters (PVIs). The location and phase allocation of the PVIs are considered as input parameters for the stochastic simulation. The method has been applied to three different low-voltage networks: two in Sweden and one in Germany. In the Swedish networks, for 6-kW single-phase PVIs, it is likely that the contribution from single-phase photovoltaic inverters to the voltage unbalance exceeds 1%. The 2% value is unlikely to be exceeded. In the German network, for 4.6-kW single-phase PVIs, the voltage unbalance is between 1.35% and 2.62%. The risk of high-voltage unbalance can be reduced by a combination of controlled distribution over the phases and a reduction of the maximum size for a single-phase PVI.
机译:本文提出了一种随机方法来估计具有高渗透率的单相光伏逆变器(PVI)的低压配电网络中未来的电压不平衡。 PVI的位置和相位分配被认为是随机模拟的输入参数。该方法已应用于三个不同的低压网络:两个在瑞典,一个在德国。在瑞典网络中,对于6 kW单相PVI,单相光伏逆变器对电压不平衡的贡献可能超过1%。不太可能超过2%的值。在德国网络中,对于4.6 kW单相PVI,电压不平衡在1.35%至2.62%之间。可以通过相间受控分布和减小单相PVI的最大尺寸的组合来降低高压不平衡的风险。