【24h】

Analysis of Touch Voltage in TN-S Earthing System

机译:TN-S接地系统中的接触电压分析

获取原文

摘要

This paper presents touch voltage analysis in TN-S connected earth system. For this purpose, calculation of touch voltages and touch durations (as per IEEE and International Electrotechnical Committee (IEC) standards) with equivalent formulas is done for different sizes of cable and protective conductor (PE). Cable ampacity calculations for underground cable as well as thermal sizing of cable and PE are presented. Furthermore, in this paper a novel way of improving the safety in TN-S system that is by increasing the size of PE for same cable size is investigated. It is found that not only touch voltage and body current decreases but also touch duration increases which are desirable conditions from safety point of view. Also, effect of different seasons on touch duration and body current are evaluated. Especially, in raining season when soil resistivity becomes quite low, it is shown that with increase in size of PE system can become safer.
机译:本文介绍了TN-S接地系统的触摸电压分析。为此,针对不同尺寸的电缆和保护导体(PE),使用等效公式来计算接触电压和持续时间(根据IEEE和国际电工委员会(IEC)标准)。介绍了地下电缆的电缆载流量计算以及电缆和PE的热定型。此外,在本文中,研究了一种通过增加相同电缆尺寸的PE的尺寸来提高TN-S系统安全性的新颖方法。已经发现,不仅触摸电压和体电流减小,而且触摸持续时间增加,这从安全角度来看是理想的条件。而且,评估了不同季节对触摸持续时间和体电流的影响。尤其是在雨季,土壤电阻率变得很低时,表明随着PE体系尺寸的增加,它会变得更安全。