【24h】

RULE-BASED REAL-TIME CONTROL OF A FLOW BATTERY FOR PREVENTING MINIMUM IMPORT VIOLATION

机译:基于规则的流动电池实时控制,以防止最小限度的进口违规

获取原文

摘要

Per California (CA) Rule 21, large self-generating facilities such as water agencies not only have non-export agreements with their power utility provider in place, but also have a minimum import requirement under their interconnection agreement. In this study, a minimum import violation is triggered when imported grid power falls for more than 2 seconds below 5% of nominal onsite generator capacity. Herein, we present a rule-based real time control algorithm for using a flow battery to help the Victor Valley Wastewater Reclamation Authority facility prevent minimum import violations, while increasing on-site renewable energy utilization. The battery control algorithm comprises of four stages: 1) charging, 2) discharging, 3) pre-refresh, and 4) refresh. Additionally, the control algorithm manages two flow battery packs in cooperation with each other, based on battery operational constraints. Battery operation is controlled by the energy management system based on import grid power measurements.
机译:根据加利福尼亚(CA)规则21,大型自发电设施(例如水务机构)不仅与电力公用事业供应商签订了非出口协议,而且在互连协议中还规定了最低进口要求。在本研究中,当进口电网功率下降到低于额定现场发电机容量的5%的时间超过2秒时,就会触发最小进口违规。本文中,我们提出了一种基于规则的实时控制算法,该算法使用液流电池帮助Victor Valley废水回收管理局的设施防止最低限度的进口违规,同时提高了现场可再生能源的利用率。电池控制算法包括四个阶段:1)充电,2)放电,3)预刷新和4)刷新。此外,控制算法会根据电池的运行限制相互协作管理两个液流电池组。电池管理由能源管理系统根据输入的电网功率测量值控制。